Slide 1: Model 500 Split Core Current Transformer
Grid Solutions MODEL 500 Split Core Current Transformer Window Sizes Available up to 10”x 30” Application Continuous Thermal Current Rating Factor Metering. 1.33 at 30 °C. amb. 1.0 at 55 °C. amb. Frequency Terminals are 8-32 brass studs with one flatwasher, lockwasher, 50-400 Hz and regular nut. Ins
Slide 2: Model 500 Accuracy and Dimensions
Model 500 Model 500 ACCURACY DIMENSIONS RATIO MAX. RATIO CLASS WITH NUMBER RATIO U.P.F BURDEN “A1” “A2” “A3” “B1” “B2” “B3” 301 300:5 5 % @ 1.5VA 4.1 6.4 7.3 7.1 10.0 10.9 4,000:5 401 400:5 3 % @ 2.5VA 4.1 6.4 7.3 11.7 14.5 15.4 8,000:5 501 500:5 2 % @ 2.5VA 4.1 6.4 7.3 14.1 17.0 17.9 8,000:5 601 60
Slide 3: Model 500 Split Core How to Order Rectangular CTs
Model 500 Split Model 500 Split Core How to Order Rectangulary CTs This transformer is designed for assembly to an existing electrical installation without the need for dismantling the primary bus or cables. Caution: Proper safety precautions must be followed during installation by a trained electri